Introduction

Hydro-matic HMC-1 is a microprocessor-based digital thermostat designed to control chilled water systems. The HMC-1 is capable of controlling multi-stage compressor and heater outputs. This document supports the two models available: the 2-Station Hydro-matic (1 to 2 stage compressor/heater) and the 4-Station Hydro-matic (1 to 4 stage compressor/heater). Each control is available in either reverse cycle or chill cycle for 120 VAC or 240 VAC. The Hydro-matic is factory configured to customer specifications for operating voltage, cycle functions (reverse or chill) and the number of compressor stages.

IMPORTANT: Verify that the Programmable Options meet your specific system requirements before powering up your system.

System Features

Staging Delays

Microprocessor controlled staging delays insure that all the complex inter-timing functions of the system are automatically maintained.

Separate heating and cooling modes

By the push of a single button, the system automatically switches all external hardware to the desired Mode (heat or cool).

Programmable protection level

The failsafe level can be programmed to fit individual requirements.

User configurable output voltage

The external contactors circuits used to control the actual compressors and heaters can be made to be any voltage from 12 VAC to 120 VAC for low voltage outputs where safety and cost are major considerations.

User Over-ride switches

The user can over-ride the control systems by simply enabling or disabling any combination of the controlled hardware. A multi-colored LED indication is supplied when this function is in use.

Dual Display Capability

As with many large vessels it may be advantageous to have one display in the Captain's or Engineer's quarters and another locally at the system's site. Hydro-matic can support two control panels for convenient use in remote locations.

Automated valve unloading

The Hydro-matic unloads the head pressure of the compressor via the optional unloading valves, enabling easier compressor starts.

Intelligent compressor sequencing

The Hydro-matic sequentially rotates the use of the leading or starting compressor in order to equalize each compressor's cumulative run time.

Failed compressor bypass

The Hydro-matic will automatically bypass and replace a failed compressor stage and will continue to compensate staging functions while maintaining cooling or heating operations.

Operator Controls & Display Panel

Please refer to Figure 1: Hydro-matic Display Panel for the following discussion:

1. Outlet Temp Display

The seven segment LED display indicates outlet water temperature, program function (in Program Mode) and sensor information (in View Mode).

2. Inlet Temp Display

This seven segment LED display indicates inlet water temperature, program parameter value (in Program Mode) and sensor readings (in View Mode).

3. Cool LED

When this LED is illuminated, the Hydro-matic is in Cool Mode.

4. Heat LED

When this LED is illuminated, the Hydro-matic is in Heat Mode.

5. Compressor LEDs

These LEDs indicate the active states of the compressors in the system.

6. Heater LEDs

These LEDs indicate the active states of the heaters in the system.

7. Power LED

When this LED is illuminated, it indicates that the Hydro-matic is operational (in the On Mode).

8. Service LED

When this LED is illuminated, it indicates that the Hydro-matic has detected a fault condition.

9. MODE Button

This button switches between Cool and Heat Mode.

10. View Mode

This button is used to view the sensor status in On Mode. In Program Mode, this button is used to select the programmable items.

11. ON/OFF Button

This button turns the control on and off. It is also used to enter Program Mode and to initialize Factory Default Values.

12. SELECT Button

This button changes the program values in Program Mode, is used to exit View Mode, and removes flashing fault codes from the display.

Control Board Switches and Indicators see page 6A

There are 14 Override Switches on the Hydro-matic Control Board; one for each output. These switches are three position switches. Accompanying these switches are multi-color LED indicators that show what position the switch is in.

Placing an Override switch in the Green position sets the output for Automatic or normal operation. The center OFF position sets the output to OFF or De-energized state. Placing the switch in the position Red sets the output to ON or energized state.

IMPORTANT: Extreme caution must be exercised when switching the override switches while the system is powered on! Improper random staging or improper settings can result in extreme electrical current loading and possible electrical damage. These switches should only be used by experienced personnel with a deliberate plan of intent.

Modes of Operation

Off Mode

When the Hydro-matic is in the Off Mode, all control outputs will be turned off, and the display will be quiescent. Restoring Factory Defaults and Program Mode can only be accessed via Off Mode.

On Mode

This is the primary operating mode of the Hydro-matic. Power will be supplied to the appropriate outputs as required, and all the other modes are accessible to the user. Temperatures in the display will be updated every ten (10) seconds for small changes, but responds immediately for large changes.

Cool Mode

When the Hydro-matic is in Cool Mode, the system will provide cooling when required

Heat Mode

Selecting Heat Mode causes the hydro-matic to provide heating when required.

View Mode

View Mode allows the user to examine the system's sensors and line voltage.

Program Mode

Program Mode allows the user to change any of the various program settings.

Using the Hydro-matic

To Turn the Unit On

Press the ON/OFF button once. This toggles the Hydro-matic from the Off Mode to the On Mode. The panel displays will light, indicating that the unit is ready for operation.

To Turn the Unit Off

Press the ON/OFF button once to toggle the Hydro-matic from the On Mode to the Off Mode.

Selecting Cooling or Heating

Pressing the MODE button toggles between Cool and Heat modes. The Cool or Heat LED will be lit, indicating which mode is currently selected. Only one of these modes can be active at a time.

Using View Mode

Enter View Mode by pressing the VIEW button. View mode will sequentially display each installed item as indicated in Table 1.

The sensor number is displayed in the OUTLET TEMP display, and the sensor reading is displayed in the INLET TEMP display. Only sensors that are actually equipped are displayed.

Table 1: View Mode Displays

To exit View Mode, press the SELECT button. The Hydro-matic will automatically exit View Mode if no buttons are pressed for 30 seconds.

Program Mode

The Program Mode is used to view and/or change the user-programmable options. The Hydro-matic is shipped with Factory Default Settings of these programmable parameters which are stored in permanent memory, and can be recalled at any time.

IMPORTANT: The Factory Default Settings may not be compatible with your equipment! If you need to customize the default parameters, read page 7.

Note: Severe electrical disturbances can sometimes upset the Hydro-matic's operating sequences. Operator confusion related to program parameters can also cause what seem to be operational problems.

Whenever there is any doubt as to the proper operation of the Hydro-matic control unit, factory default parameters should be initialized.

Important: It is important to insure that the system has been shut down prior to programming the Hydro-matic to avoid any electrical problems. During the programming session, all control outputs are switched off automatically. If any program parameters are changed, the unit will perform a power-on reset before powering back up.

Entering Program Mode

The Program mode can be entered from Off mode only. Table 2: Programming Quick Guide provides information about the programmable options available, factory default values and the allowable range for each setting.

To enter program mode, press and hold the ON/OFF button until a "P" appears in the Outlet Temp display [approximately 4 seconds]. Release the button at this time and the first program menu item will appear in the Outlet Temp display ("P 1"). The View button is used to sequentially display each program item.

Using Program Mode

The current program settings are displayed in the Inlet Temp display. The Select button is used to change the program settings: Pressing and holding the Select button will increment the setting value. Releasing and then pressing and holding the Select button will decrement the program setting value. The rate at which the program values change will increase after 5 seconds. Releasing the button at the desired value will set the value for that program, and saves the change in permanent memory.

Exiting Program Mode

To exit Program Mode, press the ON/OFF button once. When exiting, the Operating Voltage and the Firmware Version Number are displayed. The Hydro-matic will automatically exit Program Mode if no buttons are pressed for 30 seconds. The voltage and firmware revision are not displayed in this case.

Restoring Factory Default Settings

From OFF Mode ONLY: Initialize the Factory Default Settings by pressing and holding the ON/OFF button until "IP" appears in the Outlet Temp display, indicating that the initialization process has been completed. Releasing the button momentarily displays the Operating Voltage and the Firmware Version Number.

ProgrammingMAS Settings Not Saved

The MAS settings are NOT embedded in the factory code. If the factory default settings are restored the Marine Air Settings must be reset manually.

Programming Change Notice

Program parameters P-1 thru P-14 have default values set by the Hydro-Matic circuit board. Marine Air Systems { MAS } resets program items P-1, P-2, P-5, & P-12. Parameters P-10 & P-11 may also be reset depending on the chiller.

MAS Program Values

P-1 = 110°F [ 43°C ], P-2 = 48°F [ 9°C ], P-5 = 30 seconds, P-12 = 2, P-10 & P-11 may need to be reset as per the chiller specifications. See Table 2 on page 10 for all other settings.

Hydro-Matic Override Toggle Switches

The Hydro-Matic has 14 override toggle switches that control the terminal block connections from COMP-1 to Sea-Pump consecutively. These switches are used for trouble shooting purposes to override the thermostat outlet and inlet sensors, the service sensors connected to the sea water coils, and the high and low pressure switches. Multicolored LED's above the toggle switches indicate which position the switches are in. Switching the toggle Up will show a red light and force the selected output On. When an output is forced On, all the above listed safety devices are overridden. Selecting the center position will show no light indicating the output to that device is turned Off. Switching the toggle down will indicate a green light enabling the outputs' safety devices and returning control to the system processor. This is the normal operating mode for the Hydro-Matic control. See drawing H0020001 on page 28.

Trouble Shooting With the Override Toggle Switches

If there is a system fault follow these steps:

1) Check the flow switch indicator lights on the electrical box door. If the green flow switch light is Off there is NO flow through the chilled water coils and manifolds. Older model chillers will show a red light On, indicating no chilled water flow. First check the chilled water pump, if the pump is not running switch its' toggle Up. If the pump runs with the toggle Up, the fault is in the Hydro-Matic board, not in the pump. Next check if the chilled water coils are frozen, if so then they will need to be thawed. Reverse cycle chillers can be thawed by forcing the unit into heat with the override compressor and valve toggle switches. Electric heat chillers can be thawed by using the chilled water pump and the heater override toggle switches. Possible reasons for coil freezing are: Poor chilled water flow, low Freon charge or the thermostat is set too low.

2) Switch all compressor toggles Up overriding the inlet and outlet thermostats, sea water condenser coil service sensors, and the high and low Freon pressure switches.

a} If all the compressors run the fault is one of the above mentioned safety devices. Check the Hydro-Matic display for a fault code and refer to page 19.

b} If only one compressor is NOT running, then the fault is that compressors' Freeze-Stat.

c} If No compressors are running the fault is the High Limit Switch.

d} See " How to Diagnose Control Circuit Components" in the Chillers' Manual.

3) If a sea water coil freezes in the reverse cycle mode, turn the valve toggle Off [center position] and override the compressor [toggle up with red LED] until the coil thaws. Possible reasons for coil freezing are: Poor sea water flow, low Freon charge, or the sea water is too cold for heating.

4) If the sea water coil gets too hot in the cool mode then the problem is in the sea water system. First check the sea water pump, if it runs with the switch up then the fault is in the Hydro-Matic. Next check the sea water strainer and clean if necessary. Then check the sea water inlet and outlet fittings for obstructions. Also inspect hose and hose connections for leaks, kinks and air traps. Clean the sea water coils if necessary.

Program Parameter Table

Table 2: Programming Quick Guide

P-1. Heat Set Point

This function sets the temperature for the control to be satisfied when it is in heating mode. In other words, heating is called for when the water temperature falls below this value. It has a range of 95º F to 118º F (35º to 48º C). The factory default setting is 108ºF (42ºC). The Marine Air setting is 110ºF (43ºC)

Use the Select button to change the heat set point value.

P-2. Cool Set Point

This function sets the temperature for the control to be satisfied when it is in cooling mode. In other words, cooling is called for when the water temperature rises above this value. It has a range of 42º F to 58º F (5.6º to 14º C). The factory default setting setting is 49º F (9º C). The marine Air setting is 48°F (9°C).

Use the Select button to change the cool set point.

P-3. Heat Staging Temperature

This selects the temperature spread for the heaters or compressors when the Hydro-matic is in heating mode. The inlet water temperature has to drop below the Heat Set Point minus the Heat Staging Temperature in order for the first compressor or heater to turn on. (See the section Theory of Operation for a more detailed description of the heating cycle) This function has a range from 1-6ºF (1-3ºC). The factory default value is 2º.

Use the Select button to change the heat staging temperature.

P-4. Cool Staging Temperature

This selects the temperature spread for the compressors when the Hydro-matic is in cooling mode. The inlet water temperature has to rise above the Cool Set Point plus the Cool Staging Temperature in order for the first compressor to turn on. (See the section Theory of Operation for a more detailed description of the cooling cycle) This function has a range from 1º to 6ºF (1º to 3ºC). The factory default value is 2ºF or C.

Use the Select button to change the cool staging temperature.

P-5. Staging Time Delay

This program adjusts the time delay between the starting of compressors and/or heaters to prevent more than one turning on at the same time. It is the same for both heating and cooling modes. The allowable delay time range is 30 seconds to 200 seconds. The factory default value is 60 seconds. The marine Air Setting is 30 seconds.

Use the Select button to change staging time delay.

P-6. Service Sensor High Temperature Limit

The high temperature limit determines the maximum water temperature for the system before a fault condition is flagged. The temperature range for this limit is 120º F to 145º F (49º - 63º C). the factory default value is 135º F (57º C).

Use the Select button to change service sensor high temperature limit.

P-7. Service Sensor Low Temperature Limit

The service sensor low temperature limit determines whether compressors or heaters are to be used in heating mode on reverse cycle applications and if heaters are equipped. The temperature range for this limit is 25º F to 45º F (-4º to 7º C). The factory default is 35º F (2º C).

Use the Select button to change the service sensor low temperature limit.

P-8. Failsafe level

This programming option determines the actions that the Hydro-matic takes upon detection of a fault condition (see section on Failsafe Protocols for specific details of particular faults). There are 3 levels of fail-safe protection provided:

Level 0 No failsafe protection

No action taken

Level 1 Service LED Only on Fault Detection

No action taken

Level 2 Maximum Failsafe Protection

Compressor Shut Down on Fault Detection

The factory default value is protection Level 2. Use the Select button to change the Protection Level.

P-9. Sea Pump Operation

This program option selects whether the sea water pump is on all the time (continuous) or only on when the compressor is on..

0 selects Continuous Pump (factory default).

1 selects Cycle with Compressor.

P10. Number of Heaters Equipped

This setting allows for programming the number of heaters in the system. The range is 0 to 4 (or 2 for 2-station units). The factory default setting is 4 on 4-station hydro-matics (2 on 2-station units).

P11. Number of Compressors Equipped

This setting allows for programming the number of compressors in the system. The allowable range is 1 to 4 (or 2 for 2-station units). The factory default setting is 4 for 4-station hydro-matics (2 for 2-station units).

P12. Sensors Equipped

Use the chart below to determine the correct code to enter for the sensors attached to the system:

The allowable range of number is 0-7. The factory default is 1. The marine Air setting is 2.

P13. Line Voltage Limit

This option programs the minimum operating voltage allowed before a low power fault is detected. Valid ranges for this parameter are 80 to 100 VAC (for 110 VAC systems) and 180 to 200 VAC (for 220 VAC systems). The factory default setting is 80 VAC for a 110 Volt system and 180 VAC for a 220 Volt system.

P14. Temperature Units

This option selects either the Fahrenheit or Celsius temperature scales for display.

0 selects degrees Fahrenheit.

1 selects degrees Celsius.

Theory of Operation

Heating/Cooling Cycles

The Cooling and Heating cycles are controlled by four factors: the inlet water temperature, the current operating mode (Heat or Cool), the programmed set point (items P-1 and P-2), and the programmed Staging Temperature (items P-3 and P-4). Please note that there are separate set points and staging temperatures for heating and cooling.

The control algorithm is the same for both heating and cooling. In Cool Mode, the control is satisfied when the inlet water temperature reaches the programmed Cool Set point (P-2). In Heat Mode, the control is satisfied when the inlet water temperature reaches the programmed Heat Set point (P-1).

The following discussion assumes system cooling. Figure 2, Cooling Cycle illustrates this example. There are four staging levels of cooling. Level 0 corresponds to the programmed set point. Levels 1 through 4 are separated by the programmed staging temperature.

The cooling cycle starts when the inlet water temperature rises above Level 1. At this time, a lead compressor is selected and turned on. Once the inlet water temperature reaches Level 0, the compressor will be turned off and the cooling cycle is ended. The lead compressor is changed (advanced) each time to allow for equal use of all compressors. If the inlet water temperature rises above level 2 during a cooling cycle, the Hydro-matic enables a second compressor. This second compressor will be turned off when the inlet water temperature drops below Level 1. The third and fourth compressors are utilized in the same way, being turned on and off as the inlet water temperature rises above and falls below their particular programmed staging temperatures. Figures 3 through 6 illustrate the system timing of this algorithm under the various heating and cooling modes.

In addition, there is a programmable Staging Time Delay (P-5) to prevent more than one compressor (or heater) from turning on at the same time. This programmable staging time is the same for both Heat Mode and Cool Mode.

The decision to use a compressor or a heater in Heat Mode is made by comparing the condenser sea water temperature to the programmed Service Sensor Low Temperature Limit (P-7). If the sea water temperature is above the limit, then compressors are used. If the sea water temperatures below the limit, then heaters are used. Either heaters or compressors are used, never a combination. The Hydro-matic selects the next available compressor (unless a water temperature sensor fault exists) for the temperature test. If no compressors are available, the program shuts down the last compressor enabled for two minutes. After the two minutes, the temperature is tested and the compressor is released for operation. If there are no heaters equipped, then the test for water temperature is not performed and compressors are used for heating at all times.

Electric Heaters [JMP1 & JMP2]

Four (4) station boards equipped with electric heaters and no reverse cycle heat need to have both JMP1 and JMP2 jumpers installed. This allows the heaters to follow the loop water temperature requirements without regard to the service sensor temperature. JMP1 and JMP2 are located next to the systems one MHz crystal and microprocessor.

The electric heater contactors must be connect the heater outputs on the Hydro-Matic board.

P-10 should be programmed for the correct number of heaters connected.

NOTE… Two Station Boards require jumper JMP1 removed and jumper JMP2 installed for this same option.

Optional Unloader Valves

The optional unloader valves provide the logic to release residual pressure from the system. Their relative timing logic is illustrated in Figures 3 through 6 for both Chill cycle and Reverse cycle operating modes. The unloader valves can be directly connected to the Hydro-matic control board without the use of contactors.

fig 3: System Timing for Reverse Cycle Cooling

fig 4: System Timing for Reverse Cycle Heating

fig 5: System Timing for Chill Cycle Cooling

fig 6: System Timing for Chill Cycle Heating

Fault Detection and Failsafe Protocols

Pressure and temperature sensors are monitored for abnormal indications, which may then be flagged as faults.

Failsafe Protection

There are three levels of reaction to faults detected by the Hydro-matic:

Level 0 is the lowest level of protection; non "fatal" faults will be suppressed, and there will be no indications to the user that a fault occurred.

Level 1 is the intermediate level of protection; non "fatal" faults will be flagged and displayed, but no other actions will be taken.

Level 2 is the maximum level of protection provided; the hydromatic will indicate when a fault has occurred and will also shut down system components as required.

Fatal faults are conditions that, if they occur, could damage the control and/or system components. For this reason, reaction to these faults is mandatory and are not part of a limited failsafe scheme.

The following table lists the faults that can be detected and the action taken by the Hydro-matic for all three protection levels:

When a fault is detected, it is reported and acted upon according to the programmed failsafe level (P-8). If the service LED is turned on, the Outlet Temp display will also provide a flashing fault code. If the Hydro-matic is required to take a compressor off line because of the fault, the LED for that compressor will flash, indicating that an error has been detected.

If it is desired that the flashing fault code be removed from the display, then press the Select button. This does not, however clear the fault or return the compressor to on line status.

Inlet temperature and Low Voltage faults will result in the complete shutdown of the system. The system will remain shut down until the faults are cleared.

A compressor pressure fault (High Freon or Low Oil) is defined to be an open contact detected on a pressure sensor for a compressor that has been running at least 15 seconds. A Low Freon Pressure fault is defined to be an open contact on a pressure sensor for a compressor that has been running at least 4 minutes.

If the compressors are shut down but not taken off line when the fault occurs, the Service LED and fault code will be displayed for approximately 1 second.

Compressor Lockout occurs when three (3) successive pressure faults are detected during one heating or cooling cycle. At this point, the failed compressor(s) is (are) taken off line. To clear the fault and return the compressor(s) back to on line status after the problem has been checked and corrected, the control must be turned off (ON/OFF button), and then back on.

Line Voltage Failsafe Protocols

Line Voltage

The Hydro-matic monitors the input line voltage. This is used to protect the chiller system hardware and the Hydro-matic.

A-C will be displayed in the Outlet Temp display if the line voltage drops below the level set with the Line Voltage Limit option (P-13) during normal operation of the Hydro-matic. All outputs will be shut down until the voltage rises above the programmed limit.

If the Hydro-matic is connected to improper voltage during initial power-up, the following messages will be displayed:

A-C

A Low Power on AC Line Fault (AC) will occur if a system configured for 220V is connected to a 110V supply. "A-C" will flash in the outlet temp display and the Hydro-matic will shut down all outputs.

HPF

A High Power Fault (HPF) will occur if a system configured for 110V is connected to a 220V supply. "HPF" will be alternating between both the Inlet and Outlet Temp displays and the Hydro-matic will shut down all outputs.

IMPORTANT: If this condition has occurred, power must be removed immediately to avoid damage to the Hydromatic and associated hardware.

Sensor Installation Notes

Service Sensor Installation

The Service sensor should be installed on the condenser coil between the first and second coil opposite the hot gas input, which is usually on the same side as the water outlet. A stainless steel strap should be used to secure it firmly to the condenser.

figure 7: Service Sensor Installation

Water Sensor Installation

Each water sensor should be mounted on the inlet and outlet pipes as shown below. A stainless steel strap (such as a hose clamp) should be used to attach the sensor to the pipe.

figure 8: Water Sensor Installation

Applications

Product Specifications

Jumper Settings & Part Numbers

Twenty-Four Volt Control Voltage

• JUMPERS EXT-L1 AND EXT-L2 REMOVED

4 Station Cooling Only

• JMP 1 IN AND JMP 2 IN

• PART NO. ASY-220-A15 115 VOLT

• PART NO. ASY-220-A22 220 VOLT

• PART NO. ASY-220-C15 115 VOLT 24 VOLT CONTROL

• PART NO. ASY-220-C22 220 VOLT 24 VOLT CONTROL

4 Station Reverse Cycle Heating & Cooling

• JMP 1 IN AND JMP 2 OUT

• PART NO. ASY-220-B15 115 VOLT

• PART NO. ASY-220-B22 220 VOLT

• PART NO. ASY-220-D15 115 VOLT 24 VOLT CONTROL

• PART NO. ASY-220-D22 220 VOLT 24 VOLT CONTROL

2 Station Cooling Only

• JMP 1 OUT AND JMP 2 IN

• PART NO. ASY-221-A15 115 VOLT

• PART NO. ASY-221-A22 220 VOLT

• PART NO. ASY-221-C15 115 VOLT 24 VOLT CONTROL

• PART NO. ASY-221-C22 220 VOLT 24 VOLT CONTROL

2 Station Reverse Cycle Heating & Cooling

• JMP 1 OUT AND JMP 2 OUT

• PART NO. ASY-221-B15 115 VOLT

• PART NO. ASY-221-B22 220 VOLT

• PART NO. ASY-221-D15 115 VOLT 24 VOLT CONTROL

• PART NO. ASY-221-D22 220 VOLT 24 VOLT CONTROL